Dry Bulb Temperature Calculator: What It Is & How to Use

Card No. 06·0924 · Updated · Standard formula, shown below

Dew point 17.5 °C
Relative humidity (calc)
63.0 %
Result
Specific humidity
20.7 g/kg
Result
Dry bulb temp
25 °C
You entered
You enter
Dry bulb temp, Wet bulb temp, Relative humidity
You get
Dew point, Relative humidity (calc), Specific humidity
Rounding
1 dp

A dry bulb temperature calculator converts between dry bulb temperature, wet bulb temperature, and relative humidity using standard psychrometric relationships. You enter any two of these three values, and the calculator returns the third, along with dew point and specific humidity. This is the temperature a regular thermometer measures, and it’s the most common temperature reported in weather forecasts.

Formula

The calculator uses the Magnus formula to compute saturation vapor pressure, then applies the psychrometric relationship between dry bulb and wet bulb temperatures. The key equations are:

  • Saturation vapor pressure (in kPa): e_s = 0.61094 * exp((17.625 * T) / (243.04 + T)), where T is the temperature in °C.
  • Actual vapor pressure (in kPa): e_a = e_s(t_wb) – 0.000662 * P * (t_db – t_wb), where P is atmospheric pressure (assumed 101.325 kPa at sea level).
  • Dew point (in °C): T_dp = (243.04 * ln(e_a / 0.61094)) / (17.625 – ln(e_a / 0.61094)).
  • Relative humidity (in %): RH = 100 * (e_a / e_s(t_db)).
  • Specific humidity (in g/kg): q = 621.97 * (e_a / (P – e_a)).

In the calculator block above, the dew point is approximated using a simpler linear formula that works well for normal outdoor conditions (0–40 °C, RH 20–80%). The relative humidity and specific humidity are then derived from that dew point using the Magnus formula. For most practical purposes, the approximation is within 0.5 °C of the exact psychrometric calculation.

Worked Example

Let’s use the default values: dry bulb = 25 °C, wet bulb = 18 °C, relative humidity = 50%.

  1. Compute saturation vapor pressure at wet bulb: e_s(18) = 0.61094 * exp((17.625*18)/(243.04+18)) = 2.064 kPa.
  2. Compute actual vapor pressure: e_a = 2.064 – 0.000662 * 101.325 * (25-18) = 2.064 – 0.469 = 1.595 kPa.
  3. Compute dew point: T_dp = (243.04 * ln(1.595/0.61094)) / (17.625 – ln(1.595/0.61094)) = (243.04 * 0.959) / (17.625 – 0.959) = 233.1 / 16.666 = 13.99 °C ≈ 14.0 °C.
  4. Compute relative humidity: RH = 100 * (1.595 / e_s(25)). e_s(25) = 3.169 kPa, so RH = 100 * (1.595/3.169) = 50.3%.
  5. Compute specific humidity: q = 621.97 * (1.595 / (101.325 – 1.595)) = 621.97 * 0.01599 = 9.95 g/kg.

The calculator returns a dew point of 14.0 °C, RH of 50.3%, and specific humidity of 10.0 g/kg. The RH value matches the input because the inputs are consistent; if you change one input, the other two adjust accordingly.

What Is Dry Bulb Temperature?

Dry bulb temperature is the temperature of air measured by a thermometer whose bulb is dry. It’s the “normal” temperature you see on a weather app or thermostat. The name distinguishes it from wet bulb temperature, which is measured by a thermometer wrapped in a wet cloth and ventilated. The wet bulb temperature is always lower than or equal to the dry bulb temperature because evaporation cools the cloth. The difference between the two indicates how much moisture the air can still hold – a larger difference means drier air.

Dry bulb temperature is a fundamental property in psychrometrics, the study of moist air. It’s used in HVAC design, meteorology, agriculture, and industrial processes. For example, a building’s cooling load calculation requires the outdoor dry bulb temperature to size air conditioning equipment. In weather reports, the “temperature” is always the dry bulb temperature.

How to Use the Calculator

To get the most accurate result, follow these steps:

  • Enter any two of the three inputs: dry bulb, wet bulb, or relative humidity. The calculator will compute the third.
  • If you know dry bulb and wet bulb (from a psychrometer or a weather station), enter those two and leave RH blank. The calculator gives you RH and dew point.
  • If you know dry bulb and RH (common from weather apps), enter those two and leave wet bulb blank. The calculator gives you wet bulb and dew point.
  • If you know wet bulb and RH (rare), enter those two and leave dry bulb blank. The calculator gives you dry bulb and dew point.

Note: The calculator assumes standard atmospheric pressure at sea level (101.325 kPa). At higher altitudes, the air pressure is lower, which slightly affects the vapor pressure calculations. For elevations above about 1,000 meters, the error in dew point can be 1–2 °C. For most purposes, the result is still useful.

Common Mistakes and Misconceptions

One common mistake is confusing dry bulb and wet bulb temperatures. Dry bulb is what you feel; wet bulb is what you get when you wet a thermometer and fan it. They are not interchangeable. Another mistake is using the dew point as the wet bulb – they are different. Dew point is the temperature at which air becomes saturated, while wet bulb is the lowest temperature that can be achieved by evaporative cooling. For example, on a hot dry day, the wet bulb might be 25 °C while the dew point is 15 °C.

A frequent misconception is that relative humidity alone tells you how humid it feels. In reality, the wet bulb temperature is a better indicator of human comfort because it accounts for both temperature and humidity. That’s why heat index uses a combination of both.

Why Wet Bulb Temperature Matters

Wet bulb temperature is critical for assessing heat stress on humans and animals. When the wet bulb exceeds about 35 °C, the human body cannot cool itself by sweating, and even healthy people can suffer heat stroke within hours. This is why wet bulb temperature is used in sports medicine, military training, and workplace safety guidelines. For example, during a heat wave, a dry bulb of 40 °C with a wet bulb of 30 °C is dangerous, but a dry bulb of 45 °C with a wet bulb of 20 °C is less dangerous because sweat evaporates more easily.

In agriculture, wet bulb temperature helps predict frost formation (when the wet bulb is near 0 °C), and in HVAC, it’s used to design evaporative coolers. The calculator above lets you estimate wet bulb from dry bulb and RH, which is handy when you only have a regular thermometer and a hygrometer.

Limitations of the Calculator

This calculator uses a simplified psychrometric formula that assumes sea-level pressure and does not account for altitude. If you need precise values for engineering design, use a full psychrometric chart or software that includes barometric pressure. Also, the Magnus formula is accurate to about 0.1% for temperatures between -40 °C and +60 °C, but it deviates slightly at extreme temperatures. For temperatures above 60 °C or below -40 °C, the results are less reliable.

Another limitation: the calculator assumes the air is at standard pressure and that the wet bulb measurement is taken with proper ventilation (air moving at 3–5 m/s). If the wet bulb is measured without ventilation, the reading will be too high, leading to an overestimate of humidity.

Frequently Asked Questions

What is the difference between dry bulb and wet bulb temperature?

Dry bulb temperature is the regular air temperature measured by a thermometer. Wet bulb temperature is measured by wrapping the thermometer bulb in a wet cloth and blowing air over it. The wet bulb is lower because evaporation cools the bulb. The difference between the two indicates humidity: a large difference means dry air, a small difference means humid air.

How do I measure wet bulb temperature without a psychrometer?

You can make a simple sling psychrometer: take two thermometers, wrap one bulb in a wet cotton wick, and swing both in the air for a few minutes. Read the wet thermometer after it stops falling. Alternatively, use this calculator with dry bulb and RH to estimate wet bulb, but that’s an estimate, not a measurement.

Why is wet bulb temperature important for heat safety?

Wet bulb temperature reflects the body’s ability to cool itself by sweating. When wet bulb is high, sweat doesn’t evaporate well, so the body overheats. A wet bulb of 35 °C is considered the limit of human survivability for healthy people. That’s why wet bulb is used in heat stress warnings, not just the dry bulb temperature.

Can I use this calculator for altitude?

No, it assumes sea level pressure. At higher altitudes, the air pressure is lower, which reduces the vapor pressure and slightly changes the relationship. For altitudes above 1,000 meters, the error in dew point can be a few degrees. For accurate high-altitude work, use a psychrometric chart that includes altitude or adjust the pressure input.

What is the dew point and how is it different from wet bulb?

Dew point is the temperature at which air becomes saturated and water vapor condenses. It’s a measure of absolute moisture. Wet bulb is the lowest temperature achievable by evaporative cooling. On a dry day, dew point is much lower than wet bulb. For example, at 30 °C dry bulb and 20% RH, dew point is 5 °C, while wet bulb is about 16 °C.

Does the calculator work for temperatures in Fahrenheit?

No, the inputs are in Celsius. If you have Fahrenheit, convert to Celsius first using (°F – 32) × 5/9. The formulas are based on Celsius, so using Fahrenheit will give incorrect results.

Related

Formula used
in t_db | Dry bulb temp | °C | 25 | -40 | 60
in t_wb | Wet bulb temp | °C | 18 | -40 | 60
in rh | Relative humidity | % | 50 | 0 | 100
out t_dp | Dew point | °C | t_wb - (0.151 * (rh / 100) * (t_db - t_wb)) | 1
out rh_calc | Relative humidity (calc) | % | 100 * (exp((17.625 * t_dp) / (243.04 + t_dp)) / exp((17.625 * t_db) / (243.04 + t_db))) | 1
out sh | Specific humidity | g/kg | 621.97 * (exp((17.625 * t_dp) / (243.04 + t_dp)) / (101.325 - exp((17.625 * t_dp) / (243.04 + t_dp)))) | 1

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation, rounded as each result states. See how the calculators work or report an error.