A voltage drop calculator estimates how much voltage is lost along a conductor when current flows through it, using the load current, conductor length, material, and wire size. Enter those values and the circuit voltage if you want the percentage drop; the result is an estimate, not a wire-sizing or electrical-safety approval.
Formula
This calculator uses the resistance of a conductor and Ohm’s law. For a simplified circuit with equal outgoing and return conductors, the estimated voltage drop is:
ΔV = k × I × ρ × (L × 0.3048) ÷ (A × 10−6)
- ΔV is voltage drop in volts (V).
- k is 2 for direct current (DC) or single-phase AC, and approximately 1.732 (√3) for a balanced three-phase circuit.
- I is load current in amperes (A).
- ρ is conductor resistivity in ohm-metres: 1.724 × 10−8 for copper or 2.826 × 10−8 for aluminum in this estimate.
- L is one-way length in feet; 0.3048 converts feet to metres.
- A is conductor cross-sectional area in square millimetres; 10−6 converts it to square metres.
The displayed percentage is 100 × ΔV ÷ V, where V is the circuit voltage. Estimated load voltage is V − ΔV. The resistance model assumes a conductor at the reference resistivity and does not account for every real-world condition.
Worked Example
Using the calculator’s default values—120 V, 10 A, 50 ft one-way length, 2.08 mm² conductor area, copper, and DC or single-phase—the calculation is:
- Convert the length: 50 ft × 0.3048 = 15.24 m.
- Convert the area: 2.08 mm² × 10−6 = 0.00000208 m².
- Find the estimated drop: 2 × 10 A × 1.724 × 10−8 Ω·m × 15.24 m ÷ 0.00000208 m² = 2.527 V, or 2.53 V rounded to two decimal places.
- Percentage drop: 100 × 2.527 ÷ 120 = 2.106%, or 2.11%.
- Estimated load voltage: 120 − 2.527 = 117.473 V, or 117.47 V.
What the Inputs Mean
Length means the distance from the source to the load in one direction. The calculator accounts for the return path by using a factor of 2 for DC and single-phase circuits. Do not double the length yourself before entering it, or the estimate will count the return path twice.
Area is the conductor’s cross-sectional area, not its diameter. The default 2.08 mm² is close to the nominal area of 14 AWG copper, but wire gauges and actual conductor dimensions are not interchangeable with a precise area in every product. If you know the conductor’s material and size, use specifications for that exact cable rather than relying on a rough gauge conversion.
The circuit-type selector uses the common simplified relationship for a balanced three-phase circuit. Select it only when that model fits the circuit. For AC circuits, conductor reactance and power factor may matter, especially with long runs, larger conductors, or particular loads; this resistive estimate does not model those effects.
How to Use and Interpret the Result
Enter the nominal source voltage, expected load current, one-way route length, and conductor area. Choose the conductor material and circuit type. The first result is the estimated drop in volts; the following results express it as a percentage of source voltage and estimate the voltage at the load.
For example, the worked example’s 2.53 V drop is about 2.11% of 120 V. A percentage makes it easier to compare circuits at different nominal voltages, but it does not by itself establish whether a particular installation is acceptable. Applicable requirements and equipment specifications depend on the installation and must be checked separately.
Use consistent units. This calculator accepts feet and square millimetres; many references instead give length in metres and area in circular mils or AWG. Convert carefully before entering values. A larger conductor area generally reduces the estimated drop, while greater length or current increases it.
Accuracy, Assumptions, and Safety
Conductor resistance rises as temperature rises, so actual voltage drop can be greater than a room-temperature estimate. The selected resistivity values are reference figures, not a guarantee for a particular cable. Connections, splices, terminal condition, conductor stranding, and operating temperature can also affect a real circuit.
Voltage drop is only one consideration in choosing conductors. This calculator does not determine a safe conductor size, ampacity, overcurrent protection, grounding, installation method, or compliance with electrical codes. Those depend on factors such as insulation rating, ambient temperature, bundling, equipment, and local rules. Do not use the output as a substitute for a qualified electrician or applicable electrical standards.
The model is most useful as a first-pass estimate for a simple resistive calculation. For precision on AC circuits, use an appropriate method that includes conductor impedance, power factor, frequency, temperature, and circuit configuration. If a load has changing current, calculate for the relevant operating condition rather than assuming a convenient average.
Frequently Asked Questions
How do you calculate voltage drop?
Estimate conductor resistance from resistivity, length, and cross-sectional area, then multiply by current. For a simple DC or single-phase circuit, include both outgoing and return conductors; for balanced three-phase calculations, a √3 factor is commonly used.
Is wire length one-way or round-trip?
Enter one-way length in this calculator. Its circuit factor accounts for the return path in DC and single-phase circuits. Entering round-trip length would count that path twice.
Does a voltage drop calculator tell me what wire size to use?
No. This calculator estimates voltage drop for a conductor area you provide. It does not establish safe ampacity or an approved wire size; consult applicable electrical requirements and a qualified professional.
Why is my actual voltage drop higher than the estimate?
Higher conductor temperature, actual cable resistance, connections, load variation, and AC reactance can all increase the measured drop. The calculator uses a simplified resistive model and nominal material values.
Can I use this for three-phase power?
The three-phase option estimates a balanced circuit using a √3 factor. It may not represent an unbalanced load or an AC installation where impedance and power factor materially affect the result.
Related
Formula used
in v | Circuit voltage | V | 120 | 0 | 1000000 in i | Load current | A | 10 | 0 in l | One-way conductor length | ft | 50 | 0 in a | Conductor area | mm^2 | 2.08 | 0 sel m | Conductor material resistivity | Copper=1.724e-8, Aluminum=2.826e-8 sel c | Circuit type | DC or single-phase=2, Three-phase=1.732 out drop | Voltage drop | V | c * i * (m * l * 0.3048 / a * 1e-6) | 2 out pct | Voltage drop | % | 100 * drop / v | 2 out end | Estimated load voltage | V | v - drop | 2
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation, rounded as each result states. See how the calculators work or report an error.
More cards in this drawer
- Measuring Light Speed & Wavelength: How It Works
- Draco Race Blox Fruits: How to Get It
- ES File Explorer Tips & Tricks That Actually Work
- Remove Google FRP Lock on Oppo: Step-by-Step
- Forza Horizon 6: Unlock Legend Island & Earn Horizon Legend
- Clean Hair Dryer Filter: Improve Airflow