Data Center Cooling & Water Use Explained

Card No. 06·38900 · Updated · Standard formula, shown below

This guide explains how data center cooling systems work and why water consumption varies so much between facilities. You’ll learn the main cooling architectures—air, evaporative, and liquid—and the factors that drive water usage, from climate to server density. No special equipment is needed, just a basic understanding of how data centers operate.

What You’ll Need

  • No tools or materials are required.
  • A basic understanding of how servers generate heat is helpful.

Step-by-Step

Step 1: Understand Why Cooling Is Needed

Servers convert almost all the electricity they consume into heat. A typical rack of servers can generate 10 to 40 kilowatts of heat, and high-density racks can exceed 50 kW. Without cooling, temperatures quickly exceed the safe operating range (usually 18–27°C / 64–80°F), causing hardware failures and reduced lifespan. Cooling systems remove this heat to keep the equipment within the manufacturer’s specifications.

Step 2: Learn the Basic Cooling Loop

Most data center cooling systems work on the same principle: transfer heat from the server room to the outside environment. The basic loop has three stages:

  1. Heat capture: Air or liquid absorbs heat from the servers.
  2. Heat transfer: The warmed medium moves to a cooling unit (like a chiller or cooling tower).
  3. Heat rejection: The heat is expelled to the outside air or water.

Step 3: Identify the Main Cooling Architectures

There are three primary ways data centers remove heat:

  • Air cooling (CRAC/CRAH): Computer Room Air Conditioners or Air Handlers blow cold air through raised floors or ducts. The warm air returns to the unit, where a coil filled with chilled water or refrigerant absorbs the heat. This is the most common method for older and less dense facilities.
  • Evaporative cooling: Uses water evaporation to cool the air directly (direct evaporative) or to cool the water in a cooling tower (indirect). This is very water-intensive but uses less electricity than chillers.
  • Liquid cooling: Coolant flows directly to the server components via cold plates or immersion tanks. This is far more efficient at removing high heat loads and can reduce or eliminate the need for chillers, but it requires a separate water loop.

Step 4: See How Water Fits Into the Picture

Water is used in two main ways:

  • Cooling towers: These reject heat by evaporating water. A typical cooling tower evaporates about 1.8 gallons (6.8 liters) of water per ton-hour of cooling. The evaporation is what cools the remaining water, which then returns to the chiller or heat exchanger.
  • Direct evaporative cooling: Air is passed over wet pads or sprayed with water; the evaporation cools the air directly. This uses even more water per unit of cooling than a cooling tower because the water is not recirculated.
  • Chilled water systems: Chillers themselves use water as a refrigerant loop, but the water is closed-loop and does not evaporate. However, the chiller’s condenser may be cooled by a cooling tower, which does consume water.

Step 5: Understand Why Water Use Varies

Water consumption varies widely—from zero (fully air-cooled with no evaporative component) to several million gallons per day for large hyperscale facilities. The main drivers are:

  • Climate: In hot, dry climates, evaporative cooling is very effective but uses more water because evaporation rates are higher. In cool, humid climates, chillers can run less often, and cooling towers evaporate less water.
  • Cooling technology: Direct evaporative cooling uses the most water per unit of heat removed. Cooling towers use less, and closed-loop chillers use almost none (except for makeup water to replace leaks).
  • Server density: High-density racks generate more heat, requiring more cooling capacity, which can increase water use if the system relies on evaporative methods.
  • Water efficiency measures: Some facilities use water-side economizers (using outside air to cool the water) or dry coolers that use no water at all. Others recycle water or use treated effluent.
  • Time of year: Seasonal changes affect both temperature and humidity, directly impacting evaporation rates and cooling demand.

Step 6: Calculate Water Usage (Optional)

To estimate a facility’s water consumption, you need three numbers:

  1. Cooling load in tons (1 ton = 12,000 BTU/hour = 3.5 kW).
  2. Hours of operation (usually 8,760 hours per year).
  3. Water consumption rate for the cooling technology (typically 1.8–2.4 gallons per ton-hour for cooling towers, 3–5 gallons for direct evaporative).

Multiply the load by hours and by the rate to get annual water use. For example, a 1,000-ton cooling tower operating 8,760 hours at 2 gallons/ton-hour uses 17.5 million gallons per year.

Common Mistakes

  • Assuming all water use is equal: Evaporative cooling consumes water, but closed-loop chilled water systems only lose water to leaks and blowdown (draining to remove mineral buildup).
  • Ignoring humidity: In humid climates, evaporative cooling is less effective and may require more energy, but the water consumption is lower because evaporation is slower.
  • Mixing up power and cooling units: A kilowatt of IT load is not the same as a kilowatt of cooling capacity. Cooling systems have inefficiencies (Coefficient of Performance, COP), so a 1 kW IT load may require 1.2–1.5 kW of cooling power.
  • Forgetting blowdown: Cooling towers must periodically discharge water to prevent mineral scale. This “blowdown� adds to total water consumption, typically 10–20% of the evaporated volume.

Tips

  • Look up the facility’s PUE (Power Usage Effectiveness) and WUE (Water Usage Effectiveness) to compare efficiency. WUE is liters of water per kilowatt-hour of IT energy.
  • Use free cooling (economizers) when outside temperatures are low—this reduces chiller use and often water consumption.
  • Consider liquid cooling for high-density racks; it can eliminate the need for chillers and significantly reduce water use.
  • Regularly inspect and maintain cooling towers to minimize drift (water lost as mist) and leaks.
  • Use treated water or recycled water to reduce the environmental impact of water consumption.

Troubleshooting

Problem: The cooling system is using more water than expected.

  • Check for leaks in the water loop or cooling tower basin.
  • Verify that the blowdown schedule is not too frequent—this can waste water.
  • Ensure the cooling tower fill material is clean; scale or algae reduces heat transfer, forcing the system to run more.
  • Confirm that the water treatment system is working to prevent scale, which can increase blowdown needs.

Problem: The facility is not meeting cooling demands.

  • Check airflow distribution—hot spots may require higher fan speeds, increasing energy use.
  • Inspect for blocked vents or perforated tiles.
  • Verify that the chiller setpoint is appropriate; raising it slightly can reduce energy use without harming equipment.

Frequently Asked Questions

Do all data centers use water?

No. Some data centers use only air-cooled chillers with dry coolers (radiators) that reject heat without evaporating water. These facilities have zero water consumption for cooling, though they may still use water for humidification or domestic use.

How much water does a typical data center use?

It varies enormously. A small 1 MW facility using cooling towers might use about 4,000–6,000 gallons (15,000–23,000 liters) per day. A large hyperscale facility of 100 MW could use over 500,000 gallons (1.9 million liters) per day, depending on climate and design.

Why do some data centers use water when they could use air?

Evaporative cooling is often more energy-efficient than chillers, especially in hot, dry climates. Using water can reduce electricity consumption, which lowers carbon emissions. The trade-off is water consumption, so facilities weigh local water availability and cost.

What is WUE?

Water Usage Effectiveness is a metric that measures water consumption per unit of IT energy. It’s calculated as: WUE = (total water used in liters) / (IT equipment energy in kWh). A lower WUE means better water efficiency.

Can data centers recycle water?

Yes. Many facilities use treated municipal wastewater or recycle their own water. Cooling tower blowdown can be treated and reused. Some designs use a closed-loop water system that requires very little makeup water.

Does liquid cooling eliminate water use?

Not entirely. Liquid cooling uses a coolant loop that may be water-based, but the heat is ultimately rejected to the outside—often via a dry cooler that uses no water. However, some liquid-cooled systems still use a cooling tower for the final heat rejection, which does consume water.