This calculator determines the mixed air temperature when two air streams with different temperatures and flow rates combine, such as outdoor ventilation air mixing with return air in an HVAC system. You enter the temperature and flow rate of each stream, and the calculator returns the resulting mixed air temperature and the flow-weighted contribution of each stream.
Formula
The mixed air temperature is the flow-weighted average of the two individual stream temperatures:
Tmix = (T₁ × Q₁ + T₂ × Q₂) / (Q₁ + Q₂)
- T₁, T₂ = dry-bulb temperature of each air stream (°C or °F)
- Q₁, Q₂ = volumetric flow rate of each air stream (m³/s, L/s, CFM, etc.)
The formula assumes constant air density and specific heat, which is accurate for typical HVAC temperature ranges (±50°C). It is essentially a weighted average where the weights are the flow rates.
Worked Example
Using the default values: Stream 1 at 22°C with 0.5 m³/s, Stream 2 at 35°C with 0.2 m³/s.
- Multiply each temperature by its flow: 22 × 0.5 = 11; 35 × 0.2 = 7
- Sum these products: 11 + 7 = 18
- Sum the flow rates: 0.5 + 0.2 = 0.7 m³/s
- Divide: 18 / 0.7 = 25.7°C
The mixed air temperature is 25.7°C, and stream 1 contributes 71.4% of the total flow.
Why Mixed Air Temperature Matters
HVAC engineers and technicians use this calculation to predict the temperature of air entering a cooling coil or heat recovery unit. It affects coil sizing, energy consumption, and comfort control. For example, in a building with 20% outdoor air at 35°C and 80% return air at 24°C, the mixed air temperature is about 26.2°C. This tells you how much cooling is needed before air is distributed.
The same principle applies to:
- Economizer operation – determining when outdoor air is cool enough to use for free cooling
- Exhaust and makeup air systems – mixing building exhaust with fresh air
- Industrial drying or ventilation – blending hot process air with ambient air
How to Use the Calculator
Enter the temperature and flow rate for each air stream. The units for temperature and flow do not need to match between streams, but they must be consistent within each stream. For instance, you can use °F for both temperatures and CFM for both flows. The calculator will still produce the correct mixed temperature because the formula is linear.
Flow rate can be measured with a pitot tube, anemometer, or from fan curves. If you only know the mass flow rate (kg/s), you can use it directly – the formula works for any flow unit as long as both streams use the same one.
Common Mistakes and Limitations
One frequent error is using temperatures in Celsius and Fahrenheit together. Always convert to a single scale first. Another is forgetting that the formula assumes no heat transfer to or from the duct walls. In reality, long uninsulated ducts can slightly change the temperature, but for most calculations this is negligible.
The formula also assumes dry air. If the air streams have significantly different humidity levels, the enthalpy (total heat) mixing is more accurate, but the dry-bulb temperature mixing is still a good approximation for sensible heat calculations. For precise work, especially near saturation, use a psychrometric chart.
Also note that volumetric flow rates vary with temperature and density. If you are mixing very hot or very cold air, use mass flow rates for accuracy. For typical HVAC ranges (0–50°C), volumetric flow is acceptable.
Alternatives and Related Calculations
When humidity matters, calculate mixed air enthalpy instead: hmix = (h₁×m₁ + h₂×m₂) / (m₁ + m₂), where h is specific enthalpy and m is mass flow. This gives the true energy balance. Some HVAC software uses the bin method to average temperatures over a season, which is a more complex version of the same idea.
For three or more air streams, extend the formula: Tmix = Σ(Tᵢ × Qᵢ) / ΣQᵢ. The calculator above handles two streams, which covers most mixing boxes and ventilation systems.
Frequently Asked Questions
Can I use this for mixing water or other fluids? Yes, the same flow-weighted average applies to any fluid with constant specific heat. For water, the error is minimal over typical temperature ranges.
What if the flow rates are in different units? Convert them to the same unit first. For example, 1 m³/s = 1000 L/s = 2118.9 CFM. Use the calculator after converting both flows to a common unit.
Does altitude affect the mixed air temperature? The formula itself is independent of altitude, but if you use volumetric flow rates, lower density at high altitude means less mass flow for the same volume. Use mass flow for high-altitude or extreme temperature applications.
Is the mixed air temperature the same as the supply air temperature? No, the supply air temperature is after the cooling or heating coil. The mixed air temperature is what enters the coil. The coil then conditions it to the desired supply temperature.
How do I measure the flow rate of each stream? Use a flow hood at diffusers, a pitot tube traverse in ducts, or calculate from fan performance data. For outdoor air, you can also use a balometer or measure the pressure drop across an intake louver.
What is a typical mixed air temperature for a commercial building? It varies widely, but with 20% outdoor air at 35°C and 80% return at 24°C, the mixed air is about 26°C. In mild climates, it can be close to the return air temperature.
Related
Formula used
in t1 | Temperature stream 1 | °C | 22 | -273.15 | 200 in f1 | Flow rate stream 1 | m³/s | 0.5 | 0 | 1000 in t2 | Temperature stream 2 | °C | 35 | -273.15 | 200 in f2 | Flow rate stream 2 | m³/s | 0.2 | 0 | 1000 out tmix | Mixed air temperature | °C | (t1 * f1 + t2 * f2) / (f1 + f2) | 1 out frac1 | Fraction from stream 1 | % | f1 / (f1 + f2) * 100 | 1
Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work
Method: the standard formula for this calculation, rounded as each result states. See how the calculators work or report an error.
More cards in this drawer
- Measuring Light Speed & Wavelength: How It Works
- Draco Race Blox Fruits: How to Get It
- ES File Explorer Tips & Tricks That Actually Work
- Remove Google FRP Lock on Oppo: Step-by-Step
- Forza Horizon 6: Unlock Legend Island & Earn Horizon Legend
- Clean Hair Dryer Filter: Improve Airflow