Off Coil Temperature Calculator: How It Works

Card No. 06·1199 · Updated · Standard formula, shown below

Leaving air temp (°C) 12.40 °C
Bypass factor
0.15
Result
Entering air temp (°C)
26 °C
You entered
Apparatus dew point (°C)
10 °C
You entered
You enter
Entering air temp (°C), Apparatus dew point (°C), Contact factor
You get
Leaving air temp (°C), Bypass factor
Rounding
2 dp

An off coil temperature calculator works out the temperature of air leaving a cooling coil, given the entering air conditions and the coil’s contact factor. You enter the mixed air dry-bulb temperature, the coil’s apparatus dew point, and the contact factor, and you get the leaving air dry-bulb temperature, which is essential for sizing HVAC equipment and predicting indoor humidity.

Formula

The off coil temperature is calculated using the contact factor (also called the effectiveness or coil bypass factor). The formula is:

Tleaving = Tentering − CF × (Tentering − TADP)

Where:

  • Tleaving = dry-bulb temperature of air leaving the coil (°C or °F)
  • Tentering = dry-bulb temperature of air entering the coil (°C or °F)
  • CF = contact factor (dimensionless, between 0 and 1)
  • TADP = apparatus dew point, the average surface temperature of the coil (°C or °F)

The bypass factor is simply 1 − CF. A contact factor of 0.85 means 85% of the air contacts the coil surface and is cooled to the ADP; the remaining 15% bypasses the coil without being cooled.

Worked Example

Using the default values from the calculator:

  • Entering air temperature = 26°C
  • Apparatus dew point = 10°C
  • Contact factor = 0.85

Plug into the formula:

Tleaving = 26 − 0.85 × (26 − 10)

Tleaving = 26 − 0.85 × 16

Tleaving = 26 − 13.6

Tleaving = 12.4°C

So the air leaving the coil is at 12.4°C dry-bulb. The bypass factor is 1 − 0.85 = 0.15 (15%).

Why Off Coil Temperature Matters

The off coil temperature directly affects the supply air temperature to a conditioned space. If it is too high, the space won’t cool adequately and humidity may remain high. If it is too low, you may waste energy and create uncomfortably cold drafts. HVAC engineers use this value to select cooling coils, determine the required chilled water flow, and design duct insulation. It also helps predict the dew point of the supply air, which is critical for avoiding condensation on duct surfaces.

How to Choose the Contact Factor

The contact factor depends on the coil design and air velocity. Typical values are:

  • 4-row coil: 0.75–0.85
  • 6-row coil: 0.85–0.92
  • 8-row coil: 0.92–0.97

Higher contact factors mean more rows, deeper coils, or lower face velocity. For a rough estimate, use 0.85 for a standard 4-row coil, but check the manufacturer’s data for a specific unit. The apparatus dew point is usually provided by the coil manufacturer or can be estimated from the chilled water temperature and the coil’s effectiveness.

Common Mistakes and Misconceptions

A frequent error is using the chilled water supply temperature instead of the apparatus dew point. The ADP is always higher than the chilled water temperature because the coil surface has a temperature gradient. Another mistake is forgetting to convert between °C and °F – the formula works in either unit as long as you are consistent. Also, the off coil temperature is a dry-bulb temperature, not a wet-bulb or dew point. People sometimes confuse the leaving air temperature with the dew point of the supply air, but they are different: the leaving air dry-bulb is what the thermometer reads, while the dew point is the temperature at which moisture condenses out of that air.

Limitations of the Simple Formula

This formula assumes a constant coil surface temperature and uniform air distribution. In reality, the coil’s performance varies with airflow, fin spacing, and moisture condensation. The contact factor is not truly constant – it changes with operating conditions. For precise engineering, you should use a psychrometric chart or software that accounts for enthalpy and humidity ratio. The simple formula is a good first approximation for preliminary sizing and for checking whether a coil is performing as expected.

Frequently Asked Questions

What is the difference between off coil temperature and supply air temperature?

The off coil temperature is the air temperature immediately after the cooling coil. Supply air temperature is measured after any duct heat gain or loss, and after any reheat. In practice, they are close, but supply air may be warmer if the duct is in a hot attic or cooler if the duct is insulated and the air picks up no heat.

How do I find the apparatus dew point?

Manufacturers provide the ADP for their coils at various conditions. If you don’t have that data, you can estimate it by plotting the entering and leaving air conditions on a psychrometric chart and drawing a straight line through them – the point where the line intersects the saturation curve is the ADP.

Can I use this calculator for heating coils?

No, this calculator is for cooling coils. For heating, the analogous concept is the heating coil’s effectiveness, but the formula is different because the apparatus dew point doesn’t apply.

What is a good contact factor for a residential AC?

Residential evaporator coils typically have contact factors between 0.7 and 0.85. A higher contact factor means better dehumidification, but also more pressure drop and higher cost. Most residential units are 3-4 rows, so 0.75–0.85 is typical.

Why does my off coil temperature seem too high?

If the leaving air is warmer than expected, the contact factor may be lower than assumed, the chilled water flow might be insufficient, or the coil could be dirty. Check the coil fins and the water temperature to diagnose.

Related

Formula used
in t_enter | Entering air temp (°C) | °C | 26 | -273.15 | 100
in adp | Apparatus dew point (°C) | °C | 10 | -273.15 | 100
in cf | Contact factor | - | 0.85 | 0 | 1
out t_leave | Leaving air temp (°C) | °C | t_enter - cf * (t_enter - adp) | 2
out bypass | Bypass factor | - | 1 - cf | 2

Each line is one input (in, sel, list) or one result (out: label, unit, formula, decimals). How the calculators work

Method: the standard formula for this calculation, rounded as each result states. See how the calculators work or report an error.